An Efficient Fuzzy Logic Fault Detection and Identification Method of Photovoltaic Inverters

2021-12-16MokhtarAlyandHegazyRezk

Computers Materials&Continua 2021年5期

Mokhtar Aly and Hegazy Rezk

1Department of Electrical Engineering,Aswan University,Aswan,81542,Egypt

2Electronics Engineering Department,Universidad Tecnica Federico Santa Maria,Valparaiso,2390123,Chile

3College of Engineering at Wadi Addawaser,Prince Sattam Bin Abdulaziz University,Wadi Addawaser,11991,Saudi Arabia

4Electrical Engineering Department,Faculty of Engineering,Minia University,Minia,61111,Egypt

Abstract:Fuzzy logic control (FLC) systems have found wide utilization in several industrial applications.This paper proposes a fuzzy logic-based fault detection and identification method for open-circuit switch fault in grid-tied photovoltaic(PV)inverters.Large installations and ambitious plans have been recently achieved for PV systems as clean and renewable power generation sources due to their improved environmental impacts and availability everywhere.Power converters represent the main parts for the grid integration of PV systems.However,PV power converters contain several power switches that construct their circuits.The power switches in PV systems are highly subjected to high stresses due to the continuously varying operating conditions.Moreover,the grid-tied systems represent nonlinear systems and the system model parameters are changing continuously.Consequently,the grid-tied PV systems have a nonlinear factor and the fault detection and identification(FDI)methods based on using mathematical models become more complex.The proposed fuzzy logic-based FDI(FL-FDI)method is based on employing the fuzzy logic concept for detecting and identifying the location of various switch faults.The proposed FL-FDI method is designed and extracted from the analysis and comparison of the various measured voltage/current components for the control purposes.Therefore,the proposed FL-FDI method does not require additional components or measurement circuits.Additionally,the proposed method can detect the faulty condition and also identify the location of the faulty switch for replacement and maintenance purposes.The proposed method can detect the faulty condition within only a single fundamental line period without the need for additional sensors and/or performing complex calculations or precise models.The proposed FL-FDI method is tested on the widely used T-type PV inverter system,wherein there are twelve different switches and the FDI process represents a challenging task.The results shows the superior and accurate performance of the proposed FL-FDI method.

Keywords:Fault detection and identification;fuzzy logic;T-type inverter;photovoltaic (PV)

1 Introduction

Recently,photovoltaic (PV) generation systems have found wide concerns in electricity generation due to the reductions in the reserves of fossil fuel sources [1].Additionally,the negative impacts on environment and the global warming concerns represent the main issues of the conventional fossil fuel generations.This in turn has resulted in increasing the installed PV systems in the utility grids in addition to the ambitious future installation plans.The recent energy reports show that the electricity generation by PV systems is increasing exponentially [2].

The increased installations and the dependency of future grids on the PV generation system have increased potential for the reliability,energy efficiency,and cost reduction as major concerns for industry and research [3,4].The field based statistics have showed that the power converters of PV systems are the most vulnerable part amongst the other parts.Power converters are mainly constructed of electrolytic capacitors,power switches,and passive elements.The power switches related failures are the most common types of shutdown of PV systems [5-7].Therefore,detection of the power switches faults and identify their locations are very important for reliable operation of PV generation systems.

From another side,multilevel inverters have proven superior performance over the traditional two-level topologies for wide output power ranges [8].The main playing factors behind these advantages are the low dv/dtvalues,reduced harmonics,and low voltage ratings of components.Moreover,the output grid filter components are reduced by using multilevel inverter topologies.This in turn results in reducing volume,weight,and cost of PV systems.There are several multilevel inverter topologies in the literature for the grid-tied PV installations.Among the various existing topologies,the T-type three-level inverter topology has been widely presented from research and industry [9,10].The main advantages of T-type topology are the elimination of clamping diodes and flying capacitors,using lower rating switches,and reducing the conduction losses in the power switches.

The continuous power supply of PV systems requires the fast detection of abnormal conditions due to faults and transients.The accurate and fast detection of faults would reduce the number and time of maintenance and repair of faulty parts [11].Mainly,there are two different types of faults in power switches,including the open circuit fault,and short circuit fault.In the short circuit faults,the system is required to shutdown to prevent accumulated damage of the other parts due to the high abnormal generated fault overcurrent [4].Normally,fuses are utilized to open the circuit of the power switch at short circuit faulty condition.Whereas,the open circuit faults introduce distortions in the output of the inverter and proper detection is highly needed.The open circuit faults in T-type inverters lead to imbalance among the dc-link capacitors,which accumulates with time and hence higher voltage stresses on the capacitors and switches are produced [12,13].Thence,accurate fault detection and identification of faulty switch location is highly important in order to increase the reliability,and stability of PV generation system supply.

Several methods have been presented in the literature for detecting the open circuit faults of both the two-level and three-level inverters [14-16].General review of the existing detection and identification methods for faults in the cascaded H-bridge (CHB) inverters has been presented in [17].In [18],fast open circuited switch fault has been proposed for fault tolerant two-level inverters in active power filter applications.The detection of the fault is achieved through comparing the voltage difference in magnitude and time between the measured and calculated output voltages.However,additional sensors and accurate model of the system are required in this type of fault detection.Another similar fault detection method for two-level and three-level NPC topology has been proposed in [18,19],however it fails at identifying the location of faults switch.Concordia transform based fault detection method has been presented in [20]using the measured output current of the inverter within the line period.Unfortunately,it require an additional fundamental period for inductive current injection to identify the place of the faulty switch.Additional methods based on ac-current slope and the zero voltage switching state have been presented in [21].Although,this method represents a slow fault detection solution due to requiring three fundamental line periods to detect and identify the faulty switch.

In [22],historical average voltage values based fault detection method has been presented for the CHB topology.The method is capable of locating the faulty switch pair without determining the faulty one.A modified method has been presented in [23]with adding another voltage sensors to locate exactly the faulty switch.A method based on the state estimators and the current residual has been proposed in [24].Although,this method neglects the dynamic behavior of multilevel inverters.From another side,the neural network has been proposed for fault detection in CHB multilevel inverter topology [25].A Real-time switch fault detection method based on 1-D convolutional neural networks (CNN) has been presented in [26].These methods can properly detect the faulty switch and its location,however,complex computation and learning data are needed in this type.Additional methods have been introduced using the simplified Fourier transform [27],observer based [28],CNN [29],and deep CNN [30],

Principal component analysis (PCA) based fault detection method has been proposed in [31].However,this method requires additional measurements,which increase the cost of the system.Application of artificial neural network and fuzzy logic methods for detection of faulty switches have been proposed in the literature [32-34].However,the existing methods fail at exactly localizing the faulty switch.Additionally,the model predictive control (MPC) methods have been employed for detecting faults in power converters [35,36].These methods employ the already estimated states against the actual measured ones to detect the faulty condition.Fuzzy logic based method for detecting the faults in two-level based motor drive applications using the measured currents has been proposed in [34].

It can be seen that the existing fault detection methods focus on the two-level inverters and motor drive applications.Whereas,the grid-tied applications are subjected to continuously varying operating conditions and parameters variations.Thence,the behavior of the grid-tied PV systems is difficult to be predicted by mathematical modelling in addition to continuous variations in the grid side impedance.Thence,nonlinearity would appear in case of open circuit faults occurrence.Therefore,this paper proposes an efficient fault detection and identification method for open circuit faults for grid-tied T-type PV inverter applications.The proposed method is based on employing the fuzzy logic for detecting and relocating the various faults.The proposed method represents a simple method with considering nonlinearities and parameter variations of grid-tied PV systems.Moreover,the proposed method eliminates the need for the additional measurement circuits and/or complex mathematical modelling.

The remaining of the paper is organized as following:the operating principle and power circuit of grid-tied T-type PV inverter is presented in Section 2.The post-fault analysis of the PV inverter is explored in Section 3.The proposed fault detection method is detailed in Section 4 with the design considerations of the proposed algorithm.The results of the selected case study and performance criteria of the proposed method are given in Section 5.Section 6 presents the conclusion of the paper.

2 Operation and Structure of Grid-Tied T-type PV Inverter

The power circuit of the three-phase grid-tied three-level T-type PV inverter topology is described in Fig.1.The topology has twelve power switches with four switches in each phase.The input dc-link voltage is equally divided among the two dc-link capacitors at steady state(vdc1=vdc2=vpv/2).The dc-link capacitors are responsible for generating the different voltage levels in the inverter.The incorporation of different twelve power switches results in making the fault detection and identification process more complex for T-type inverters.The operation of the topology can be explained as follows:each phase leg in the topology can generate one of three states (P,O,or N) according to the applied gating pulses.The associated output voltages for the three states arevdc1,0,and−vdc2,respectively.The controller has to maintain balanced voltages over the dc-link capacitors in order to avoid the voltage overstresses on the different components in the inverter system.The switches pulses for each phase leg is shown in Tab.1.

Figure 1:Grid-connected three-level T-type inverter

Table 1:The switching states and switch status of the T-type topology

Fig.2 shows the control system for the three-phase grid-tied T-type topology for the PV systems.The phase locked loop (PLL) is firstly employed to provide the grid synchronization function for the inverter.The maximum power point tracking (MPPT) block maximizes the extracted power from the PV systems at the various operating solar irradiance and ambient temperature.The MPPT controller generates the reference dc-link voltage for the inverter,which is responsible for generating thed-axis reference current.Thed-qreference frame is utilized in this paper for performing the inverter control.Theq-axis reference current is determined according to the required reactive power injection by the inverter.Two differ proportional-integral (PI)decoupled controllers are used for performing thed-q-axis current control.

Figure 2:The control structure of the grid-tied PV inverter

3 Post-Fault Analysis of T-Type Inverter

In case of open circuit fault condition,some switching states will be impossible and freewheeling diodes results in different states at the output depending on the current direction and the faulty switch location.Tab.2 shows the healthy and faulty output states of the inverter at different fault locations.It can be seen that whenSx1is open circuited,the output voltage state will remain the same at negative output grid current due to the freewheeling diode path.Whereas,at positive output current and faulty switch,the current direction will go through other freewheeling path in the neutral point switches.The same analysis can be made for the other faulty conditions.The change of the switching states at faulty condition results in the distortion of the output pole voltages,output grid currents,and dc-link capacitor voltages.The distortion is dependent on the state of the pole voltage and the direction of the grid current.In the following subsections,the analysis of the effects of different switches faults on the behavior of grid currents and the dc-link capacitor voltages are analyzed in more details for designing the proposed fault detection method.

Table 2:The effect of different faults and current direction on the states of output pole voltages

3.1 Analysis of the Output Grid Currents at Faulty Conditions

The inverter is controlled to generate a sinusoidal output currents in the normal case.At the faulty case,the path is determined by the location of faulty switch,the output current polarity,and the gating pulse.The inverter output states at faulty switchSx1is shown in Fig.3a at positive polarity of output current,and in Fig.3b for negative output current polarity.At negative output current,the path is determined by the freewheeling diodeDx1of the switch at both the healthy and faulty cases and the output voltage will remain at P state without changes.Whereas,at positive current polarity,the output current will pass through the switchSx2and diodeDx3and the pole voltage will change to state O.Similar analysis can be made for the other faulty switch cases.In case of switchSx2open circuit fault,the negative grid current will pass through diodeDx2.If the grid current is positive,the new path will be through diodeDx4and the pole voltage will take the state N.In case of switchSx3open circuit fault,the negative grid current will pass through diodeDx3.If the grid current is positive,the new path will be through diodeDx1and the pole voltage will take the state P.In case of switchSx4open circuit fault,the negative grid current will pass through diodeDx4.If the grid current is positive,the new path will be through switchSx3and diodeDx2and the pole voltage will take the state O.The performance of the output current of the inverter at the various faulty switches is shown in Fig.4.Tab.2 summarizes the output state changes at different healthy and faulty conditions.

3.2 Analysis of the dc-Link Capacitor Voltages at Faulty Conditions

The two capacitor voltages are highly influenced by the faulty switch and the applied switching states of phases a,b,and c.Fig.5 shows the effect of different switching states on the dc-link capacitor voltages.The space vectors of the inverter output are categorized according to their magnitude into zero voltage,small voltage,medium voltage,and large voltage vectors.The neutral point (NP) is left unconnected in the large and zero voltage vectors,so they do not affect the NP voltage.On the other hand,medium-voltage vectors has a connection to NP,so they affect NP voltage.The NP voltage will increase or decrease depending on the current direction of its connected phase.In small voltage vectors,one or two of the three phases are connected to the NP,so they affect the NP voltage.The P-type small-voltage vectors helps to discharge the upper capacitor,and hence the NP voltage is increased.Conversely,the N-type small-voltage vectors discharges the lower capacitor that results in decreasing the NP voltage.More details about the NP voltage analysis with space vectors can be found in [15,37].

Figure 3:Current paths at normal and faulty conditions in the power switch Sa1.(a) Positive grid current (b) Negative grid current

Figure 4:The behavior of grid current in different faulty modes.(a) Sa1 fault (b) Sa2 fault (c) Sa3 fault (d) Sa4 fault

The two dc-link capacitors are expected to have equal voltages at healthy condition.When open circuit fault occurs,a change will occur in the output pole voltage state and hence the output space vectors,as described before in Tab.3.In case switchSx1fault,the P state will be replaced with O.Consequently,some regions of the discharging of the upper capacitor will be replaced with lower capacitor discharging,and hence the upper capacitor will be higher than the lower capacitor voltage.A similar analysis can be made for other types of faults.Fig.6 shows the two dc-link capacitor voltages at different types of faults.

Figure 5:The effect of different switching space vectors on dc-link capacitors voltages.(a) PPN large voltage vector (b) PON medium voltage vector (c) POO P-type small voltage vector (d) ONN N-type small voltage vector

4 The Proposed Fault Detection Method

The operation of grid-tied PV inverter systems is subjected to several varying parameters.The output power/voltage/current are highly fluctuating with the operating solar irradiance and ambient temperature.In addition,the electrical networks are weak grids,and the grid side impedance is changing with the different operating points.Therefore,the behavior of the grid-tied PV systems is difficult to be expected by mathematical modelling due to the continuously varying grid side.This in turn imposes several challenges to the fault detection as the consequences of open circuit faults are nonlinear.Fig.7 shows the nonlinear behavior of the grid connected systems at faulty condition with uncertainty in the grid-side impedance.The aforementioned analysis of the inverter system performance under different fault types is employed for designing the proposed fuzzy logic detection technique.The grid current and dc-link capacitor voltages are the selected parameters to extract the fuzzy rules.This is advantageous due to using the already available measurements for the control purposes without requiring additional measurements.

Table 3:The rules of the fuzzy logic in the proposed method

Figure 6:The behavior of dc-link capacitor voltages at different faults.(a) Sa1 fault (b) Sa2 fault(c) Sa3 fault (d) Sa4 fault

Figure 7:Nonlinear behavior in the trajectory of the grid currents in α-β plane at Sx1 fault

Firstly,trajectory of the measured grid currents is made in theα-βplane.The resultant phasor current of the three phase system (Ir∠Φ) represents the sum of the current trajectory divided by number of data points.This trajectory is represented by a circle,which is centered in the origin at healthy case.Hence,the magnitude of the resultant will be zero at healthy condition.Whereas,the trajectory takes the shape of half-circle at any faulty switch condition with particular angle,which is dependent on the location of the faulty switch.Consequently,the resultant phasor current will have a magnitude that determines the occurrence of faulty condition when its magnitude exceeds some predefined threshold value.From another side,the angle of the resultant phasor current is dependent on the phase leg location of the faulty switch,which can give partial information about the location of the faulty switch.Fig.8 summarizes the various trajectories of the three-phase output grid currents in theα-βplane for the various fault conditions.The resultant will be compared with a threshold valueIthand the differenceIdwill be employed for distinguishing between healthy and faulty switch conditions.

The various faults result in different performance of the dc-link capacitor voltage related to the increase/decrease with respect to each others.Therefore,the difference between the two capacitors voltage (Δvdc) is used in addition to current trajectory amplitude and angle to design the fuzzy rules to properly detect the location of the faulty switch.There will be three input membership functions and one output membership function to define the fault occurrence and fault switch location.The input and output membership functions of the proposed fuzzy logic fault detection method are shown in Fig.9.Tab.3 summarize the fuzzy bases of input and output functions to locate the fault.Where,Z denotes to zero,P to positive,N to negative,X to do not matter,and NF to no fault conditions in Tab.3.The various rules are defined according to the response of the current trajectory and the difference between the capacitor voltages.The Mamdani fuzzy logic set is employed for implementing the proposed method.The defuzzification is performed by using Max-Min composition and the centroid of area method.

Additionally,the failure of power switches and/or diodes in the neutral point clamped topology results in the distortion of the inverter output current and unbalance of dc-link capacitor voltages.Therefore,the proposed method can be also applied to the neutral point clamped topology with the same aforementioned analysis and design method.The output signal of the proposed fault detection method is fed into fault tolerant control systems to take the proper post-fault action.Hence,continuous operation of PV inverter systems can be maintained with the help of the proposed fault detection method.

Figure 8:Trajectory of grid currents in α-β plane in different faulty conditions.(a) Sa1 fault(b) Sa2 fault (c) Sa3 fault (d) Sa4 fault (e) Sb1 fault (f) Sb2 fault (g) Sb3 fault (h) Sb4 fault (i) Sc1 fault (j) Sc2 fault (k) Sc3 fault (l) Sc4 fault

5 Results and Discussions

To test the feasibility and effectiveness of the proposed fault detection method,a test case study has been designed and simulated using MATLAB/SIMULINK platform.Tab.4 summarizes the PV inverter parameters for the studied system.The open-circuit faulty condition is emulated by disconnecting the gating pulses from the power switches.Fig.10 shows the performance of the output pole voltage at faulty switch ofSa1.It can be seen that the output pole voltage of phase a is distorted in the positive half-cycle of the output voltage.The output state P cannot be generated during this fault and the output state O is generated instead.Whereas,the other two pole voltages of phase b,and c are generated properly.It can be seen also due to the lag power factor of the inverter,some part of the positive pole voltage is not affected due to the freewheeling diode of the switchSa1.

The performance of the proposed fault detection method at faulty switchSa1is shown in Fig.11.The output currents of the PV inverter are distorted at the faulty condition.This is a direct result from the distortion of the output pole voltage of phase leg a.The positive half-cycle of the current is eliminated due to the fault.In the proposed method,the output currents and the dc-link capacitor voltages are employed to generate the various membership inputs to the proposed fuzzy logic based fault detection method.The fuzzy logic output of the proposed method is shown in the figure.It refers to output 1 faulty condition,which denotes to the faulty switchSa1as described in the design of the proposed method in Tab.3.Moreover,the output of the fuzzy logic is maintained at 0 output at no fault condition,which shows the ability of the proposed method to distinguish between the healthy and faulty conditions.

Figure 9:The input and output membership functions of the proposed fuzzy logic.(a) µId (b) µΦ(c) µΔvdc (d) µFO

Table 4:The system parameters for the simulated case study

The performance of the proposed method at faulty condition ofSa2is shown in Fig.12.It can be seen that the output current is distorted in the positive half-cycle of phase leg a.To determine the difference among the faulty case ofSa1andSa2,the sensed dc-link capacitor voltages are employed as inputs for the proposed method.As shown in the analysis in Fig.6,the two faults has different effects on the dc-link capacitor voltages.The output of the proposed detection method is 2 in this case,which belongs to the faultySa2condition.Therefore,the proposed method can determine the faulty condition with determining the faulty switch location.Moreover,the proposed method can detect the various faults within only a single line period.

Fig.13 shows the performance of the proposed detection method at faulty switch ofSa3.The inverter operation is affected by this faulty case,and the negative half-cycle of the output current is eliminated.The current trajectory is estimated in this type of fault,and the amplitude and phase angle are fed into the proposed method.With employing the difference between capacitor voltages as input to the proposed method,the results shows the effectiveness of the proposed method to locate the faulty case and the faulty switch location.The output of the proposed fuzzy logic method denotes to the output of 3,which belongs to the switchSa3faulty case.It is clear the ability of the proposed fault diagnosis algorithm to detect and locate the fault within one fundamental period at various types and location of faults.

Figure 10:The simulation results of the output pole voltage at fault location in switch Sa1

Figure 11:The simulation results of the proposed method performance at fault location in switch Sa1

Figure 12:The simulation results of the proposed method performance at fault location in switch Sa2

Figure 13:The simulation results of the proposed method performance at fault location in switch Sa3

6 Conclusions

An efficient fuzzy logic-based open circuit fault detection and identification method has been proposed in this paper for grid-tied PV inverters.The proposed method can deal successfully with the nonlinearities of the grid-tied PV systems and the utility grid impedance uncertainties,especially during the faults conditions.Additionally,the advantages of the proposed method are the simple implementation,no need for complex mathematical modelling,no need for large training data,and without requiring additional measurements and/or circuits.The analysis,design,and implementation of the proposed detection method are presented for the widely-used three-phase T-type three-level PV inverter topology.The performance of the measured output current and dc-link capacitor voltages are analyzed at healthy and faulty conditions for designing the fuzzy bases and for extracting the rules of the proposed fuzzy logic detection method.Furthermore,the proposed detection algorithm employs the already available measurements for the control purposed of the PV inverter.The results of the tested case study verify the superiority of the proposed detection method for detecting the various faulty conditions,and identifying the location of the faulty switch accurately.